Sign In | Join Free | My udpf.com |
|
Brand Name : GENY
Model Number : YC-1893D
Certification : ISO, CE
Place of Origin : CHINA
Payment Terms : L/C, T/T, D/P
Supply Ability : 100/Year
Model NO. : YC1893D-6 Three Phase Meter Test System
Display : Digital
Installation : Direct Connected
Usage : Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Prepayment Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter
Electric Equipment : Three-phase Three-wire
Theory : Electronic Meter
Power Meter Connection : Terminal
Measured Signal : Pulse Peak
Type : Energy Meter
Customized : Customized
Trademark : GENY
Transport Package : Plywood Case
Specification : 12.4CBM
Origin : China
HS Code : 9030849000
Port : Guangzhou, China
The three-phase meter test system with ICTs features multiple positions up to 40 meters and an accuracy class of 0.02%. It includes a multiple serial port communication system for parallel communication, ideal for testing smart meters.
Power Supply
Voltage | 3x230 / 400 V ±10%, 50 / 60 Hz ±2 Hz |
Frequency | 50 Hz ±15% |
Power capacity | > 6 kVA |
Power efficient(at full load) | ≥85% |
Ambient temperature | -10 °C -- +40 °C |
Relative humidity | 35% - 85% |
Power Source
Voltage | |
Test voltage output (Phase-Neutral) | 3x(24 – 300 V) |
Power of the voltage output | 3×1500VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | < 0.01% |
Distortion factor | < 0.3% for linear resistance load |
Harmonics | 2nd – 41st free programmable |
Current | |
Test current output | 1 mA – 120 A |
Power of the current output | 3×2000VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | < 0.01% |
Distortion factor | < 0.3% for linear resistance load |
Harmonics | 2nd – 41st free programmable |
Phase angle | |
Range | 0 -- 360° |
Resolution | 0.01° |
Setting accuracy | 0.1° |
Frequency | |
Range | 45 Hz – 65 Hz |
Resolution | 0.01 Hz |
GENY's meter test systems adopt the most advanced electronic measurement technology and modular concept combine the differential reference standards and power amplifiers to meet the requirements of customers in electric energy meter manufacturers, electric power utilities, metrology laboratory, measurement and quality inspection departments and factories or enterprises.
The YC1893D Meter Test System is a fully automatic system for testing and calibrating single phase and three phase electrical energy meters, consisting of the following components
The YC1893D meter test system is fully compliant with the IEC 60736 standard and is suitable for testing meters according to the following standards:
Users of testing equipment from GENY have the ultimate responsibility to ensure that anyone working on or near the equipment follows all relevant safety precautions. Safety measures must comply with the requirements specific to this type of testing equipment. In addition to the standard regulations that apply to the workplace, follow the below recommendations. Trained personnel with extensive testing equipment operation knowledge must conduct all work. To prevent injury or fire hazards, do not power on the machine if it is damaged or suspected to be faulty. Avoid operating the machine in damp, wet, condensing, dusty, or explosive gas environments. Incorrect equipment operation can result in hazardous situations, causing harm to the operator and damage to the machine.
![]() |
Powerful and Accurate Stationary Meter Test Equipment for Smart Meter Testing Images |